12V wire gauge calculator for RV and van solar systems

Enter the current and the cable length. The calculator picks the smallest cable that is safe and efficient, and the fuse that protects it.

Circuit voltage
Cable type and location
Printed along the cable jacket. If you cannot find it, choose 60 °C.
Only used to label the cable in your parts list.

How the wire gauge calculator works

A cable has to pass two separate tests. The calculator runs both and gives you the larger answer.

Test 1: voltage drop

Thin or long cables waste voltage as heat. The drop is:

voltage drop (V) = 2 × one-way length (ft) × current (A) × 12.9 ÷ circular mils of the cable

The 2 covers the trip out and back. 12.9 is the resistance constant for copper at a conductor temperature of 75 °C, a deliberately warm figure. The calculator finds the smallest cable whose drop is within your limit.

Test 2: ampacity and the fuse

A fuse exists to protect the cable. So the cable must be able to carry at least the fuse rating without overheating, and the fuse must be big enough not to blow in normal use. The calculator takes 125% of a continuous load, rounds up to the next standard fuse, and then finds the smallest cable rated for that fuse.

Short, high-current runs are usually decided by ampacity. Long, low-current runs are decided by voltage drop. The result tells you which one set your cable size.

Inputs explained

Insulation rating

Insulation that tolerates more heat lets the same copper carry more current. Marine-grade and welding cable are usually rated 105 °C. General-purpose automotive wire is often rated lower. The rating is printed on the jacket.

Bundles and hot spaces

Cables tied together cannot shed heat as well, and cables in an engine bay start out hot. Both reduce the safe current. The calculator applies the standard correction factors: 0.7 for three bundled cables, 0.6 for four to six, 0.5 for seven to twenty-four, and 0.85 for 105 °C cable in an engine space.

Fuse pairing

  • Fit the fuse on the positive cable, as close to the power source as you can. For a battery cable that means at the battery, not at the device.
  • A cable fed from both ends, such as the one between a charge controller and a battery, is protected at the battery end.
  • The fuse must be rated for your system voltage. Common blade and ANL fuses are 32 V parts, so a 48 V system needs fuses rated 58 V or more.
  • For the main fuse on a lithium bank, choose a type with a high interrupt rating. Class T fuses are rated to interrupt 20,000 A. Smaller terminal (MRBF) fuses are rated for 10,000 A at 14 V and less at higher voltages.

Ampacity table used

Allowable current for a single copper conductor outside engine spaces at 30 °C ambient, from Table 5 of 33 CFR 183.425. The marine standard ABYC E-11 uses the same values, and they are widely used for vehicle conversions.

AWGmm²105 °C90 °C75 °C60 °C
161.3125 A25 A15 A15 A
142.0835 A30 A20 A20 A
123.3145 A40 A25 A25 A
105.2660 A55 A40 A40 A
88.3780 A70 A65 A55 A
613.3120 A100 A95 A80 A
421.2160 A135 A125 A105 A
233.6210 A180 A170 A140 A
142.4245 A210 A195 A165 A
1/053.5285 A245 A230 A195 A
2/067.4330 A285 A265 A225 A
3/085385 A330 A310 A260 A
4/0107.2445 A385 A360 A300 A

Safety limits of this calculator

  • It never recommends less than 16 AWG for a power cable.
  • It covers single cables up to 4/0 AWG. Larger loads need parallel cables or a higher system voltage, and are worth a professional design.
  • It is for low-voltage DC wiring. Mains (120 V or 230 V AC) wiring follows different rules.
  • Equipment manuals often state a minimum cable and a maximum fuse. Where they differ from this result, follow the manual.

Common questions

What gauge wire do I need for a 2,000 W inverter at 12 V?

A 2,000 W inverter draws about 185 A from a 12 V battery at full power. For a 5 ft (1.5 m) run the calculator gives 1/0 AWG cable with a 250 A fuse. A longer run or a hot location needs a thicker cable, and the inverter manual may ask for more, so check it.

Do I enter the one-way length or the round trip?

Enter the one-way length: the distance the cable travels from the power source to the device. Current flows out on the positive and back on the negative, so the calculator doubles it for you.

What voltage drop should I allow?

Use 3% for anything that charges a battery or is sensitive to voltage: solar, chargers, inverters, fridges and electronics. Up to 10% is acceptable for simple loads such as lights. Lower is always better if the cable cost is reasonable.

Why is the recommended cable thicker than a marine wire chart shows?

Two reasons. This calculator works out voltage drop with the resistance of copper at 75 °C, which is higher than the cool-wire figure many charts use. It also makes sure the cable can carry its fuse rating, not just the load. Both choices lean towards a slightly thicker cable.

Can I use copper-clad aluminium (CCA) cable?

It is best avoided for battery and inverter cables. CCA carries about 61% as much current as copper of the same size, so it needs to be roughly two AWG sizes larger, and it is more prone to loose, hot connections. Many cheap "0 gauge" kits are CCA, so check the description.

Before you build

These results are planning estimates. They come from published formulas and tables, with the assumptions listed on this page. They cannot see your vehicle, your cable routes or your equipment. Follow the installation manual for every component, fuse every positive cable close to its power source, and have a qualified electrician check the system if you are unsure about any part of it.